Exciting new SPD installation - with cock-up! @dsesuk
Exciting new SPD installation - with cock-up!  @dsesuk
Uploaded September 2019 | Updated November 2026, 2 hours ago
**ERROR IN VID: READ DESCRIPTION!**

Yes, there is indeed a cock-up with this one. As pointed out in the pinned comment, this installation does not comply with reg 534.8 *dammit*! Let me explain why so you lot don't make the same mistake as the dashing and handsome chap in this video!

When installing an SPD externally and in parallel like I have here, the line distance counts, so the length of my tail into this board is part of the 0.5 metre length we want to be under. My tail here is perhaps about 60cm. If installing a consumer unit with a built-in SPD, then the tail length is largely irrelevant as the SPD is already close and in parallel with the final circuits inside the CU, so only the line length from the main switch/MCB to the SPD would be counted (along with the earth from SPD to the MET).

If installing an SPD externally to the CU, the best bet is something like the Wylex product shown towards the start of this video as it squashes the surge before it gets to the CU. If connecting one up in parallel such as I have here, it would need to be right at the origin of the installation, as close as you can get to the supplier's equipment.

Sorry for the mistake, I don't know how I didn't spot that in reg 534.8. My thanks to YouTube user "Number 33" for picking that up, and to the great JW for clarifying on Twitter! A follow-up video has now been uploaded addressing all this: youtu.be/1XqESpSxSPc

Those pesky knock-outs: no I couldn't reverse the DIN rail as it's not square to the board, so the cover won't fit back on unless it's upside down with the lid flapping open. Yes, I could rearrange the devices on the DIN rail, but to move the main switch left I would have to bin the busbar and install a 16mm wire to route the switch output to the MCB. It's not the case that these things can't be done, more a question of how much do I need to modify this off-the-shelf solution in order to install it!

Related videos:
youtu.be/1XqESpSxSPc - An update to this video!
dses.co.uk/index.php/free-advice/198-the-sy2-d-surge-protector-spd
youtube.com/watch?v=aLWtwjmSgHE&t=548s (GSH)
Exciting new SPD installation - with cock-up!Prat in McHat talks PAT... testingReviewing reviewersTwo dicks, one hole... and a new C.U.Half a faultSunday hangover project 1: Makita DMR104 Bluetooth HackUpper class insulation resistance fault-findingJCC lighting - the (paid) influencers favouriteLinda and me at Elex 23Goofing off to buff my P.V. stuff!Remuneration from illuminationTradecert: The Easycert Bumfister
David Savery Electrical Services |

Exciting new SPD installation - with cock-up!

SHARE TO X SHARE TO REDDIT SHARE TO FACEBOOK WALLPAPER