Arthur Fault? Bloody good bloke! Yip yip! Nah, I’m just pullin’ your Christmas cracker pal; this is a video about us *not* finding a fault. Well, we find half a circuit the fault isn’t on, but then Christmas comes along and we clock off. Should we survive the booze, food and Omicron variant, maybe we’ll post an update in the new year to show why this RCBO is tripping.
This one is less well explained, so I've thrown in some visual aids to show what we’re testing and what we’re seeing. Nonetheless, it may be a bit confusing as it’s us thinking on our feet out in the world where there’s not always a nice clear fault to easily be found.
The tripping RCBO has three circuits connected. The HomeServe chap who came before us has disconnected the circuit that has a low insulation resistance of 0.3MΩ, something we verify before we start dicking around. This is shown at the nine-minute mark.
We then restored power to the other circuits so we could see what was working and what was dead. The exterior lighting was not powered, so we started there.
At the fifteen-minute mark, we thought we’d traced the fault. An IR test on what we think are exterior bollard lights was at zero, so with those disconnected, we returned inside to test back at the board. To our dismay, the IR result was now even worse – a straight zero indicating a resistive short.
To prove a resistive short, the Metrel was switched to continuity mode at 15:47 and a test was performed between L+N and the earth bar. A reading of 1.08Ω was returned and, surprisingly, the live RCBO tripped off even though our circuit under test had been disconnected and was supposedly isolated from everything else. Naughty naughty: we should really have powered off the CU while dicking around dead testing.
The energised RCBO tripping on a continuity test for a circuit that's supposedly disconnected and isolated can only happen if our tester has found a common path to neutral i.e., if our faulty circuit’s neutral was cross connected to an energised neutral on another circuit, as that would provide a path that was resistively shorted between N-PE (they being connected together at the head).
At 16:55, I test for a neutral cross connect by continuity testing between the disconnected circuit neutral and the neutral bar. A reading of just 0.90Ω is returned where there should be no continuity between individual circuits. This explains why they shared an RCBO as splitting them would have caused tripping issues when the lights were turned on. It goes to show one shouldn't assume a disconnected circuit is always isolated, especially where it's evident a moron has been fiddling with the wiring.
AT 17:40, we figure the discrepancy between the IR figures obtained at nine minutes and fifteen minutes is because the first test was undertaken with the main switch off, so the tester recorded only the circuit earth fault which has a higher resistance and bombs out at 0.03MΩ, whereas the second test was performed with the other circuits energised, thus providing a path via a neutral cross connect, through the RCBO, through the main switch, through the connection between N & E at the head (which is a low resistance connection compared to the circuit fault), then back through the main earthing to the tester. The 1.08Ω recorded earlier was the resistance of this path.
Make sense? Crikey, try picturing it all in your head when it’s the last job before Christmas and you just want to get down the bloody boozer!
To show that the first IR reading was down to the fault and the second was down to the N-PE path through a cross-connect, that path is closed at 18:10 by knocking off the main switch and the test then repeated. The tester is forced to pass through the circuit fault again as that’s the only path now available, and this time we get a similar number to that of the nine-minute mark, 0.04MΩ.
Fault finding and correction is made much more difficult here because the electrical installation is gash and obviously the work of an amateur. I’ve said it before, but while an amateur may well get something working, that doesn’t mean it’s safe, has any longevity or that the likes of us won’t have to rip apart the walls and ceilings should it all go wrong.
The bonnie situation:
The hall, kitchen, exterior lights and ventilation are back on. The cabling tests good going into the outside bulkhead, then reads bad going out. From here it goes on to serve the two bedrooms, so they’ve been left disconnected. Partial success to date then, although we still need to find why the bedrooms are borked and that’ll likely involve opening the ceilings.
Follow up vid: youtu.be/JMrX4rOd_lQ
Don't worry, Nigel will get over his hissy fit and be back for more abuse in 2022.
A previous video where he and I were trapped in a dank cellar with no lighting and had to rub each other off is… on OnlyFans…, but another one where we had to actually fix the lights can be found here: youtu.be/-BMMoqCQCYo
Arthur Fault? Bloody good bloke! Yip yip! Nah, I’m just pullin’ your Christmas cracker pal; this is a video about us *not* finding a fault. Well, we find half a circuit the fault isn’t on, but then Christmas comes along and we clock off. Should we survive the booze, food and Omicron variant, maybe we’ll post an update in the new year to show why this RCBO is tripping.
This one is less well explained, so I've thrown in some visual aids to show what we’re testing and what we’re seeing. Nonetheless, it may be a bit confusing as it’s us thinking on our feet out in the world where there’s not always a nice clear fault to easily be found.
The tripping RCBO has three circuits connected. The HomeServe chap who came before us has disconnected the circuit that has a low insulation resistance of 0.3MΩ, something we verify before we start dicking around. This is shown at the nine-minute mark.
We then restored power to the other circuits so we could see what was working and what was dead. The exterior lighting was not powered, so we started there.
At the fifteen-minute mark, we thought we’d traced the fault. An IR test on what we think are exterior bollard lights was at zero, so with those disconnected, we returned inside to test back at the board. To our dismay, the IR result was now even worse – a straight zero indicating a resistive short.
To prove a resistive short, the Metrel was switched to continuity mode at 15:47 and a test was performed between L+N and the earth bar. A reading of 1.08Ω was returned and, surprisingly, the live RCBO tripped off even though our circuit under test had been disconnected and was supposedly isolated from everything else. Naughty naughty: we should really have powered off the CU while dicking around dead testing.
The energised RCBO tripping on a continuity test for a circuit that's supposedly disconnected and isolated can only happen if our tester has found a common path to neutral i.e., if our faulty circuit’s neutral was cross connected to an energised neutral on another circuit, as that would provide a path that was resistively shorted between N-PE (they being connected together at the head).
At 16:55, I test for a neutral cross connect by continuity testing between the disconnected circuit neutral and the neutral bar. A reading of just 0.90Ω is returned where there should be no continuity between individual circuits. This explains why they shared an RCBO as splitting them would have caused tripping issues when the lights were turned on. It goes to show one shouldn't assume a disconnected circuit is always isolated, especially where it's evident a moron has been fiddling with the wiring.
AT 17:40, we figure the discrepancy between the IR figures obtained at nine minutes and fifteen minutes is because the first test was undertaken with the main switch off, so the tester recorded only the circuit earth fault which has a higher resistance and bombs out at 0.03MΩ, whereas the second test was performed with the other circuits energised, thus providing a path via a neutral cross connect, through the RCBO, through the main switch, through the connection between N & E at the head (which is a low resistance connection compared to the circuit fault), then back through the main earthing to the tester. The 1.08Ω recorded earlier was the resistance of this path.
Make sense? Crikey, try picturing it all in your head when it’s the last job before Christmas and you just want to get down the bloody boozer!
To show that the first IR reading was down to the fault and the second was down to the N-PE path through a cross-connect, that path is closed at 18:10 by knocking off the main switch and the test then repeated. The tester is forced to pass through the circuit fault again as that’s the only path now available, and this time we get a similar number to that of the nine-minute mark, 0.04MΩ.
Fault finding and correction is made much more difficult here because the electrical installation is gash and obviously the work of an amateur. I’ve said it before, but while an amateur may well get something working, that doesn’t mean it’s safe, has any longevity or that the likes of us won’t have to rip apart the walls and ceilings should it all go wrong.
The bonnie situation:
The hall, kitchen, exterior lights and ventilation are back on. The cabling tests good going into the outside bulkhead, then reads bad going out. From here it goes on to serve the two bedrooms, so they’ve been left disconnected. Partial success to date then, although we still need to find why the bedrooms are borked and that’ll likely involve opening the ceilings.
Follow up vid: youtu.be/JMrX4rOd_lQ
Don't worry, Nigel will get over his hissy fit and be back for more abuse in 2022.
A previous video where he and I were trapped in a dank cellar with no lighting and had to rub each other off is… on OnlyFans…, but another one where we had to actually fix the lights can be found here: youtu.be/-BMMoqCQCYo
![Sunday hangover project 1: Makita DMR104 Bluetooth Hack
A boring and ill-thought-out presentation on how to bastardise a Makita DAB/FM radio with integrated Bluetooth functionality. This hack allows us to swerve the (frankly) awful pop shite spewed out by the identikit commercial radio stations, the music snobbery of BBC 6Music, the assumption of Radio 1 that all listeners are black teenagers living in London, the dinosaur presenters of Radio 2 who haven’t (yet) been subject to arrest through Operation Yewtree, the irrelevance of Radio 4 left talking to itself in many a deserted middle class kitchen, or the idiocy of Radio 5 as they interview meatheads about mundane sporting events or seek the opinion of Joe Asshole “man on the street” for his opinion on Brexit as he staggers out of Wetherspoons with slimy piss streaked down his trousers.
This isn’t a how-to guide, it’s just me: hungover, beer-gut in shot, and cocking about with Nigel’s radio on a rainy Sunday. Take it or leave it.
Nerds who want to get pissy: It works. Don’t tell me it’s shite and I’ve done it all wrong, we’ve had it out on site for two weeks and it’s working like a charm. Go back to your board games and spaffing one into a sock over that photo of your aunt who showed too much cleavage at that last family function.
Also, to address the comments about taking 5V from the USB port, its not a host port, Ive had the voltmeter across it and didnt pick up a 5V source there. Im not sure how youre supposed to update the firmware via this port, perhaps from a laptop with a microUSB cable (in which case, the laptop provides the host power). And no, theres no phone charger built into this model.
People disappointed that this isn’t directly electrical site-related: We’re in COVID-19 lockdown, and I don’t intend to spend much of it sober. It’s this or Nick bloody Bundy, and you’re not *that* desperate yet… are you?
Links:
TP Link Bluetooth Music Receiver: https://amzn.to/33N5pBe [affiliate link]
Note: this is not the item used in this video but is the one shown at the end which perhaps makes for a better job as no pairing button is needed.
Conversion of my ghetto blaster back in 2014: https://r3uk.com/index.php/tech-tips/39-cool-projects/207-the-bluetooth-ghetto-blaster
The latest model of this radio WITH Bluetooth and DAB+: https://amzn.to/2xrVNzK [affiliate link]
The current model of this radio, should you want to apply your own hack: https://amzn.to/2xmZxSU [affiliate link]
The music channel used: https://www.youtube.com/channel/UCG024cJIVAgbUHvjYV7IiQw/featured
If buying a DAB radio, get one with DAB+ to better future-proof your purchase. Sunday hangover project 1: Makita DMR104 Bluetooth Hack](https://i.ytimg.com/vi/vFlwqVLt1fc/mqdefault.jpg)









![EICR failure site - righting the wrongs
This is a follow-up video to an EICR we performed back in March 2019 where the electrical installation had exceeded the capacity of the RCD on site resulting in its mechanical failure.
Original video: https://youtu.be/cJuO7oKSDMs
The demand problem has been reduced in the following ways:
One of the three electric showers has already been decommissioned.
A second electric shower is to be decommissioned and a new one is to be installed from one of the two gas boilers.
Three of the socket circuits have been reduced to 20A.
New maximum demand calculations/measurements:
Circuit 1: Shower: 7500W 32A
Circuit 2: Shower: 7500W 32A
Circuit 3: Cooker: 4600W: 10A + 30% of remainder = 13A [diversity calculation]
Circuit 4: Cooker: 4800W: 10A + 30% of remainder = 13.27A [diversity calculation]
Circuit 5: Socket ring: 32A [no diversity]
Circuit 6: Socket ring: 12.8A [40% diversity]
Circuit 7: Socket radial: 8A [40% diversity]
Circuit 8: Socket radial: 8A [40% diversity]
Circuit 9: Socket radial: 8A [40% diversity]
Circuit 10: Socket radial: 8A [40% diversity]
Circuit 11: Shed [DB2]: 16A
Circuit 12: Water heater: 13A
Circuit 13: Lighting: 1.6A [Actual]
Circuit 14: Lighting: 0.3A [Actual]
Circuit 15: Lighting: 0.25A [Actual]
Circuit 16: Lighting: 0.5A [Actual]
Circuit 17: Lighting: 0.6A [Actual]
Circuit 18: Doorbell/lighting: 0.05A [Actual]
Circuit 19: Lighting: 0.7A [Actual]
Adding this lot up gives a new maximum demand on paper of about 200A which is twice what the main fuse is rated for. But then, this is why the maximum demand calculation is a bit of a nonsense. Those socket circuits aren’t really going to be pulling 76.8A at any given time on any given day, the shed isn’t likely to be pulling 16A, the water heater is only used when the combi boiler breaks down, etc. The problem before was three electric showers plus all the socket outlets hanging off a single 63A RCD, but now that everything has been split out there is no single point at the CU which is being exposed to more current than it is rated for.
A few additional notes not covered on camera to fend off some of the questions likely to be asked in the comments….
I would have preferred to terminate the SWA directly onto the metal CU enclosure, but the knockout on the right side of the board is 32mm. Had there been a 20mm knockout, I would have done this, but I didn’t want to holesaw one in, so I went for the quicker and easier option of terminating it onto a Wiska box with a bit of T&E then going to the board. A Wiska locking nut makes for an easy way to terminate the sheath.
As shown, CP Fusebox have said on Twitter that their Type-A small form factor RCBO’s should be out around October 2019 and should have longer neutral flyleads.
Many circuits required extending, some of which were in junction enclosures, others were extended in the box trunking using Wago connectors. This work took place a while ago, it’s just taken me some time to get organised enough to edit it together and some footage was lost, so apologies that there are one or two things not shown here.
Some people are very neat with their cable forming in consumer units, but this job took all day, and this is neat enough as far as I’m concerned. I also see some people cable tie the wires to keep them together which is a no-no as it brings grouping factors into play. For more on that, I refer you to this excellent video from SparkyNinja:
https://www.youtube.com/watch?v=e3xA3t6wAmY
A couple of pedants commented on the previous video that “FAIL” was the wrong term for an EICR and I shouldn’t have described it that way. Well, the installation FAILED to meet the criteria required by the reporting process for a ‘satisfactory’ outcome. So bore off.
Links:
CP Fusebox gear was sourced from Gil-Lec Electrical:
https://www.gil-lec.co.uk/circuit-protection/consumer-units-accessories/fusebox-consumer-units
Haste UK: http://www.hasteltd.co.uk/
YouTube channels showing CU installations and discussing Type-A RCD/RCBO’s:
CJR Electrical:
https://www.youtube.com/channel/UCoVvd6bZ6LSKv-ePiow1evg
DSS Electrical:
https://www.youtube.com/channel/UCC9nYFJuVVOuH49xR_t9vJg
Artisan Electrics:
https://www.youtube.com/channel/UCUYJhbsrC1bvVWzgUq83K4A
e5 Group:
https://www.youtube.com/channel/UCAKzna71V7xKMTlNTS3eKhA
…and may I also ask you to check out J Beck Electrical ‘cos I like the way his dick swings:
https://www.youtube.com/channel/UCkezXm0I_KhjLH_DnLXFN5A/videos