What’s that, analogue you say? Analogue??! Surely in this world of digital test instruments there’s simply no value to something with a pointy pointer that points to printed pictures of poxy numbers?! Well, maybe… but surely all those pesky Australians can’t be wrong?!
Notes:
At 5:51 I wibble on about aligning the needle through the centre of the infinity marks on the display, then after much twiddling I leave it cock-off. That’s just because the camera was in the way and I was looking at it from the side, but it goes to show how an adjustment of this sort needs to be made when facing it squarely on.
It’s also of note that I say the MFT1552 shows an electronic ‘analogue’ display ranging in voltage from 0 to 600, the latter number indicating full-scale deflection, yet the legend printed to the left of the Megger’s LCD shows no more than 500V should be applied… so that’s a bit weird and serves to make me look quite the fool.
I should also state that Megger, and the 15 or 17 series of testers, aren’t the only brand or models of digital instruments that show an analogue representation on their LCD displays. My TIS MFT Pro has such on IR, in a very basic way, and that cute Robin KTS1625 has a digitally represented scale too. Other machines have similar no doubt.
Oh, I know there's been a glut of new videos spouted out here over the past week which is most out of character. Rest assured, the next one may be weeks away!
Links:
Dave Willman showing his Hioki in action:
youtube.com/watch?v=hSd9xnXk8e8&t=685s
Farnell (perhaps the only UK retailer who flog these):
uk.farnell.com/hioki/3490/insulation-tester-4gohm-1kv-610g/dp/3234197?ICID=I-RP-STM7REC-0
Affiliate links:
The Calcard resistance and IR checker: amzn.to/3utElFE
For a shout out on the next video you can by me and Nigel a bottle of cough mixture here:
buymeacoffee.com/dseselectric
My all but abandoned Amazon storefront:
amazon.co.uk/shop/davidsaveryelectricalservices
£50 off YourTradeBase:
go.yourtradebase.com/refer/3M6F3301
SumUp credit/debit card processing:
http://r.sumup.com/referrals/oBF5S
£10 off your first Huel order when you spend £40 or more:
huel.mention-me.com/m/ol/nm0sq-david-savery
Get £40 credit for switching to Zen Internet:
zen.mention-me.com/m/ol/rt4lh-david-savery
For web hosting, get £10 off at Krystal with the code DSESELECTRIC at checkout!
krystal.uk
What’s that, analogue you say? Analogue??! Surely in this world of digital test instruments there’s simply no value to something with a pointy pointer that points to printed pictures of poxy numbers?! Well, maybe… but surely all those pesky Australians can’t be wrong?!
Notes:
At 5:51 I wibble on about aligning the needle through the centre of the infinity marks on the display, then after much twiddling I leave it cock-off. That’s just because the camera was in the way and I was looking at it from the side, but it goes to show how an adjustment of this sort needs to be made when facing it squarely on.
It’s also of note that I say the MFT1552 shows an electronic ‘analogue’ display ranging in voltage from 0 to 600, the latter number indicating full-scale deflection, yet the legend printed to the left of the Megger’s LCD shows no more than 500V should be applied… so that’s a bit weird and serves to make me look quite the fool.
I should also state that Megger, and the 15 or 17 series of testers, aren’t the only brand or models of digital instruments that show an analogue representation on their LCD displays. My TIS MFT Pro has such on IR, in a very basic way, and that cute Robin KTS1625 has a digitally represented scale too. Other machines have similar no doubt.
Oh, I know there's been a glut of new videos spouted out here over the past week which is most out of character. Rest assured, the next one may be weeks away!
Links:
Dave Willman showing his Hioki in action:
youtube.com/watch?v=hSd9xnXk8e8&t=685s
Farnell (perhaps the only UK retailer who flog these):
uk.farnell.com/hioki/3490/insulation-tester-4gohm-1kv-610g/dp/3234197?ICID=I-RP-STM7REC-0
Affiliate links:
The Calcard resistance and IR checker: amzn.to/3utElFE
For a shout out on the next video you can by me and Nigel a bottle of cough mixture here:
buymeacoffee.com/dseselectric
My all but abandoned Amazon storefront:
amazon.co.uk/shop/davidsaveryelectricalservices
£50 off YourTradeBase:
go.yourtradebase.com/refer/3M6F3301
SumUp credit/debit card processing:
http://r.sumup.com/referrals/oBF5S
£10 off your first Huel order when you spend £40 or more:
huel.mention-me.com/m/ol/nm0sq-david-savery
Get £40 credit for switching to Zen Internet:
zen.mention-me.com/m/ol/rt4lh-david-savery
For web hosting, get £10 off at Krystal with the code DSESELECTRIC at checkout!
krystal.uk
![The £85 EICR.... of pants
What bang you get for your buck when you just want it cheap... and why it might all end up as money down the drain...
Contains strong language and scenes of alcoholic ranting.
An Electrical Installation Condition Report, when properly undertaken, will give you a true picture of the ongoing safety of the electrical installation and what areas, if any, need maintenance or upgrades. Sadly, too many are being performed quickly and cheaply by people who havent been specifically trained for the task resulting in nonsense such as we see here.
A quick aside: this review of another outfits EICR paperwork was recorded on Sunday after what can only be described as a massacre of white wine in a ranty fashion, yet reviewing it in the cold light of day on Monday, I wasnt happy with how Id presented some points or the language used against those behind this abomination. I felt it was making me look like a bit of a prick which... is most out of character... as Im sure youll agree.
So, this is the theatrical edit with it depersonalised and cleaned up a little. As such, some errors and omissions, especially on the Schedule of Inspections, have been cut. There are more errors on this paperwork than this video documents. And no, there wont be a directors cut.
To preempt a few questions:
Im not sure why the video freezes around the 26:40 mark, its okay on the editor so it may be an encoding error.
Around the 8:20 mark, Ive had to blank out the website quotes as some sleuths were identifying the author of this nonsense.
The mixture of Y/N and ticks/crosses is obviously because its easier to place a Y or N in a box than the tick or cross symbol using the likes of Word or OpenOffice.
I dont know whats going on with Section K which is a malformed mess, but this is how it was presented to the client.
Why is a 2014 build being re-inspected in 2019 when the house builder would have signed it off for ten years? I dont know, but the lady had just moved in so maybe she didnt have the paperwork or wanted it checked for her own peace of mind (which she didnt get).
Im kicking myself for not taking pictures on the day, but I didnt plan to make a video out of it. It was only after I received the report that I choked on my gin & tonic and (weeks later) pulled out the video camera.
Not everyone on Checkatrade is a wanker, but in my opinion, Checkatrade are wankers.
I think I asked at the time how long the chap had been on site for, but it was three months ago, and I cant remember what the homeowner said now. Its a moot point, whether it was one hour or all day, it wasnt worth the money.
The last contact I had with the homeowner was before Christmas and she said that she was going to complain to this person about their report being incomplete and inaccurate. I dont know if she did, or where that went, and Ive lost her number so I havent chased it up, nor do I particularly have the time or inclination to as Im rammed with work.
It is possible to be a good inspector without any specific City & Guilds (or whatever) paperwork *if* you know what youre doing, understand the forms, have the insurance, and are recognised for undertaking such work by your CPS (when a member of such). My annoyance isnt with inspectors who know what theyre doing; its with installers who dont but who offer it as a service because they are either wholly ignorant of their inadequacy, or just dont care.
If you dont agree with me on bathroom sockets, and dont like the one I showed 150cm from Zone 1 but on the other side of the doorway, read up on Reg 701.32.1.
As for that Lily Allen thing, wow, that was freaky huh? I cant figure how that happened. Handy though, as I hate how she spouts shite on behalf of the masses and how she claims we working class are all thick racists when she is herself dumb as hell and only has her privileged singing career thanks to mummy and daddy being in the showbiz industry to go down on the right people. I dont know if she does take it up the arse, but youd have to pull the silver spoon out first if you did want to pot the brown.
Links:
Government planning portal approved documents:
https://www.planningportal.co.uk/info/200135/approved_documents/
Electrical Safety Firsts Best Practice Guides:
https://www.electricalsafetyfirst.org.uk/professional-resources/best-practice-guides/
e5 Group podcasts:
https://www.youtube.com/playlist?list=PLKu40BuY2wcR5Ap6EBe8oVeSoKJ-ktRUH
Electricians Guide to the Building Regulations [affiliate link]:
https://amzn.to/38Et1IX
The Electricity at Work Regulations 1989:
https://www.hse.gov.uk/pubns/books/hsr25.htm -free download
https://amzn.to/335OZU5 [published copy -published copy [affiliate link]
NAPIT Codebreakers: https://amzn.to/3f0yAF6 [affiliate link]
A map of the COVID19 spread (as Chromecast to my TV in the background)... just to worry you:
https://gisanddata.maps.arcgis.com/apps/opsdashboard/index.html#/bda7594740fd40299423467b48e9ecf6 The £85 EICR.... of pants](https://i.ytimg.com/vi/BqNZugQ1kI0/mqdefault.jpg)
![SH!T CHAT: The Klein Tough Box Cooler
An ad-hoc ramble about a cool box.
WARNING: There is (almost) no bad language in this one. Well be back on form in the next one though (probably).
Available on Amazon:
https://amzn.to/2GJ0pTI [affiliate link]
Kindly provided to us by SuperRod UK: www.super-rod.co.uk SH!T CHAT: The Klein Tough Box Cooler](https://i.ytimg.com/vi/CNFZWtogXYc/mqdefault.jpg)








![On a domestic EICR
Wobbly camerawork abounds in this video filmed ad-hoc during an Electrical Installation Condition Report performed on a domestic TT installation recorded on 27th August 2019. This is our first visit to this site, so familiarisation was required on this Victorian property whch has an extension built in the past forty years. The CU had been replaced by the previous owner as an apparent DIY job... well, at least I hope thats what it was and he hadnt paid for the cack-handedness. Still on the wall was the old 100mA RCD for fault protection, no longer needed now that all circuits are RCD protected in an insulated consumer unit as the RCDs provide disconnection of supply in the prescribed time seeing as the MCBs cant be guaranteed to because of the high Ze.
The installation was deemed as unsatisfactory on the report. Various remedials are required including sorting the Class I garage lights that are unearthed. Also, r2 was slightly high on both socket rings and one lighting circuit reported IR of only around 4 MegaOhm, but poor junctions were observed where lighting has been modified. Id like to see a second earth spike installed to try and lower that Ze a little. There were some other issues not shown here.
Western Power Distribution were called out on the day after we found a hole in the service head. Sterling service from them as always, they were there just a couple of hours later.
The laptop we use for Easycert is a refurbished Lenovo T430 available from Amazon on this affiliate link: https://amzn.to/2Lephpa - this one has a 3G modem card installed for no-hassle internet access on the go.
Despite the low battery in the camera, we had a lot of footage recorded on the day and about 25 minutes has been cut from this video to keep it at some kind of sensible length. Most of the cut footage was our form filling on Easycert, but that really deserves a video of its own rather than being shoehorned into this one. We show here one ring end-to-end, r1+r2 and IR testing, plus some testing on a lighting circuit, but r1+rn testing, RCD testing, Zs testing and the testing of most circuits is omitted from this video to prevent it being longer than the directors cut of Ben Hur.
The consumer unit is still untidy, but screws have been tightened, wires re-terminated and circuits placed into the correct terminals. The untraced circuit was pointed out to the homeowner and left switched off to allow them to spot if anything wasnt working that we may have missed.
Further links:
James Becks EICR video, now fortified with extra dog poo: https://youtu.be/rxfPFwlY0KE
Do you like daags?? https://amzn.to/2HBxbqk [affiliate link]
Kewtech croc clip leads (as I was asked about them): https://amzn.to/2Lqs8dj [affiliate link] On a domestic EICR](https://i.ytimg.com/vi/EqIL2Y6n-ec/mqdefault.jpg)