Landlords! Does your rental property wiring need to be to 18th Edition standards to comply with legislation for electrical safety in England that comes into force from July 2020 for new tenancies, or April 2021 for existing?
In this long and boring ramble where I happen to repeat myself and cut off Nigel at every opportunity, we look at an installation that was rubber-stamped by a competitor as being UNSATISFACTORY. But is it? Is it really? We’re going to reinspect it and cite our sources for any disagreement we have to the conclusions drawn under what is otherwise a fairly competent and thorough inspection by a bona fide rival inspector that cost the client £192 and left them with a remedial bill somehow amounting to £750 plus VAT.
What do you think? Do you agree with the former inspector or with our differing conclusions? Do pop up in the comments and say why but keep the discussion polite. The usual bad language has already been expunged for the most part for any landlords or letting agents who may be venturing onto this channel not knowing what to expect. There isn’t a black-and-white answer, and we have to manage the expectations of our clients without compromising the safety of the tenants based on the advice and evidence at our disposal.
Besides the HSE notice on page 13 of the Blue Book, for those wanting an actual regulation, refer to page 237 and reg 651.2, note 2: "Existing installations may have been designed and installed to conform to previous editions of BS7671, applicable at the time of their design and erection. This does not necessarily mean that they are unsafe."
Links:
A follow-up video to this:
youtu.be/drRTv9yyArs
Government guidance, which rather confusingly says you must comply with 18th Edition… unless you don’t:
gov.uk/government/publications/electrical-safety-standards-in-the-private-rented-sector-guidance-for-landlords-tenants-and-local-authorities/guide-for-landlords-electrical-safety-standards-in-the-private-rented-sector
Electrical Safety First (Best Practice Guides):
electricalsafetyfirst.org.uk/professional-resources/best-practice-guides
The Competent Persons Register from The Department for Communities and Local Government have a database of all registered electricians. Note however that there is nothing to differentiate electrical installers from electrical inspectors, so if you find someone on here, check their bona fides for performing inspection work:
competentperson.co.uk
There is also the Registered Competent Persons database where you can look up sparkies accredited through NAPIT and NICEIC to be performing electrical inspections (meaning they have been validated for the right insurance and qualifications). Many installation electricians aren’t, but still offer the service often resulting in a gash report:
electricalcompetentperson.co.uk
Speaking of gash reports, here’s one I pulled apart a few weeks ago:
youtube.com/watch?v=BqNZugQ1kI0&t=1948s
… that video being rather sweary, so here’s a link to a polite blog of the same content:
dses.co.uk/index.php/personal-blog/215-cowboy-competition-8
NAPIT Codebreakers:
amzn.to/3f0yAF6 [affiliate link]
With iCertify, whom I mention in this video, I had some back-and-forth in 2016 when I argued that the ‘Maximum permitted Zs’ column which appears on their Schedule of Test Results and auto-calculates the maximum impedance based on the particulars of the circuit should be so named; it previously being labelled as just ‘Zs’ which at face value you take to be the recorded Zs for the circuit. It took about two weeks for them to concede and re-label the column during which time they sent responses along the lines that nobody else was complaining, the head of NAPIT technical says it’s okay and I can take my business elsewhere if I don’t like it. Well excuse me for trying to offer you a simple way to improve your damn product! That, operational bugs, some horrendous interface headaches and my hatred of touchscreen devices all meant I did take my business elsewhere, and I’ve been with Easycert since. Maybe iCertify has improved; it was a long time ago. I’ll never know as I don’t intend to ever fire the knobby thing up again.
Landlords! Does your rental property wiring need to be to 18th Edition standards to comply with legislation for electrical safety in England that comes into force from July 2020 for new tenancies, or April 2021 for existing?
In this long and boring ramble where I happen to repeat myself and cut off Nigel at every opportunity, we look at an installation that was rubber-stamped by a competitor as being UNSATISFACTORY. But is it? Is it really? We’re going to reinspect it and cite our sources for any disagreement we have to the conclusions drawn under what is otherwise a fairly competent and thorough inspection by a bona fide rival inspector that cost the client £192 and left them with a remedial bill somehow amounting to £750 plus VAT.
What do you think? Do you agree with the former inspector or with our differing conclusions? Do pop up in the comments and say why but keep the discussion polite. The usual bad language has already been expunged for the most part for any landlords or letting agents who may be venturing onto this channel not knowing what to expect. There isn’t a black-and-white answer, and we have to manage the expectations of our clients without compromising the safety of the tenants based on the advice and evidence at our disposal.
Besides the HSE notice on page 13 of the Blue Book, for those wanting an actual regulation, refer to page 237 and reg 651.2, note 2: "Existing installations may have been designed and installed to conform to previous editions of BS7671, applicable at the time of their design and erection. This does not necessarily mean that they are unsafe."
Links:
A follow-up video to this:
youtu.be/drRTv9yyArs
Government guidance, which rather confusingly says you must comply with 18th Edition… unless you don’t:
gov.uk/government/publications/electrical-safety-standards-in-the-private-rented-sector-guidance-for-landlords-tenants-and-local-authorities/guide-for-landlords-electrical-safety-standards-in-the-private-rented-sector
Electrical Safety First (Best Practice Guides):
electricalsafetyfirst.org.uk/professional-resources/best-practice-guides
The Competent Persons Register from The Department for Communities and Local Government have a database of all registered electricians. Note however that there is nothing to differentiate electrical installers from electrical inspectors, so if you find someone on here, check their bona fides for performing inspection work:
competentperson.co.uk
There is also the Registered Competent Persons database where you can look up sparkies accredited through NAPIT and NICEIC to be performing electrical inspections (meaning they have been validated for the right insurance and qualifications). Many installation electricians aren’t, but still offer the service often resulting in a gash report:
electricalcompetentperson.co.uk
Speaking of gash reports, here’s one I pulled apart a few weeks ago:
youtube.com/watch?v=BqNZugQ1kI0&t=1948s
… that video being rather sweary, so here’s a link to a polite blog of the same content:
dses.co.uk/index.php/personal-blog/215-cowboy-competition-8
NAPIT Codebreakers:
amzn.to/3f0yAF6 [affiliate link]
With iCertify, whom I mention in this video, I had some back-and-forth in 2016 when I argued that the ‘Maximum permitted Zs’ column which appears on their Schedule of Test Results and auto-calculates the maximum impedance based on the particulars of the circuit should be so named; it previously being labelled as just ‘Zs’ which at face value you take to be the recorded Zs for the circuit. It took about two weeks for them to concede and re-label the column during which time they sent responses along the lines that nobody else was complaining, the head of NAPIT technical says it’s okay and I can take my business elsewhere if I don’t like it. Well excuse me for trying to offer you a simple way to improve your damn product! That, operational bugs, some horrendous interface headaches and my hatred of touchscreen devices all meant I did take my business elsewhere, and I’ve been with Easycert since. Maybe iCertify has improved; it was a long time ago. I’ll never know as I don’t intend to ever fire the knobby thing up again.




![Hot tubbery with Phil the f@%*ing Plumber
Warning! Contains a plumber: some viewers may find this distressing.
This was one of our first jobs back in the spring following Nige having been on furlough for two months and involves a hot tub going in at the request of our old mukker Phil, who… perhaps… won’t be quite so friendly toward us once he sees this video…
Anyway, there’s a lot of nonsense in this and some ‘mature’ scenes and chatter… so don’t watch it. Seriously, you don’t even get to see the flimmin’ hot-tub at the end. For anyone foolishly ignoring this sage advice, some chapters are below:
00:00 Mindless van-chat.
10:07 Phil the f***ing Plumber.
11:51 Mindless site-surveying chat.
18:25 Drilling an ‘ole.
20:25 Mindless Huel chat.
21:10 Planning the heist.
36:37 Installation begins.
1:08:18 Escape from Grafton Flyford.
Regarding hot tubs, there are different ways and means. We went for a TT install and I explain the reasons why in this presentation. That doesn’t mean it’s big, hard or clever or that we got it right… or for that matter anyone else got it wrong if they’ve done it differently. It’s simply one of those jobs where you refer to many publications to try and figure out just what you’re supposed to be doing as the guidance and manufacturers aren’t terribly helpful.
We used MCG gear from CEF, and the main reason for that being the 100ma Type-S Type-A fault protection RCD was readily available and keenly priced, plus MCG had a low-cost steel enclosure it could be housed in. They also had double-pole RCBOs, 40A C-Curve Type-AC, so it ticked all the boxes. My thanks to Lee at CEF Warwick who pulled out the stops to grab the RCBO for us from another branch at the last minute after I found I’d purchased the wrong one. Lee, we salute you!
The job as planned was for the rotary isolator to be on the back wall facing the field so it would be out of line-of-sight, but on the day, Phil asked us to place it onto the side wall. That left us short of flexi-conduit as we hadn’t brought enough for the new position. A bit of a shame as it’s less aesthetically pleasing. The patio lights are Class II, so no need to worry about simultaneous touch contact between Class I parts and TT earthing.
The testing of the 100mA RCD at the end seems to have been lost. Sorry. That was tested from the output of the device itself as, obviously, if you connect the tester downstream then the 30mA RCBO will get in the way.
My thanks to the following:
Alymazing Karaoke for musical support:
https://www.youtube.com/channel/UCG024cJIVAgbUHvjYV7IiQw/videos
Luko3artist for accepting my commission for the caricature artwork:
https://www.deviantart.com/luko3artist
https://instagram.com/luko3artist?igshid=1dqcbwt0ldsvd
https://www.youtube.com/channel/UCEr4dtAAn2iM9fqLNfqOWbg
Links:
Craig Gifford installing a hot tub using the Matt:e device:
https://www.youtube.com/watch?v=l5DjBRiwCDc&t=3s
Nick Bundy installing a hot tub on PME:
https://www.youtube.com/watch?v=usXBONOMAuQ&t=3s
Huel:
https://huel.mention-me.com/m/ol/nm0sq-david-savery
Electricians Guide to the Building Regulations:
https://amzn.to/38Et1IX [affiliate link]
IET Guidance Note 8:
https://amzn.to/30uQkCP [affiliate link] Hot tubbery with Phil the f@%*ing Plumber](https://i.ytimg.com/vi/OOCGOHFWpEQ/mqdefault.jpg)





![FFS, *AGAIN* with the SELV spike lighting!
It’s a return to basics with this vlog which would perhaps sit more at home with my content from five years ago seeing as there’s no script, no fun, no sound quality etc. I’m afraid it’s all rather been done before, not least in my “SWA Splicing and SELV garden lighting” video from April 2019. One annoyance is that I hung around specifically to be able to show you these lights at dusk, but was ejected from site two minutes after they activated, so there’s not even a satisfactory ending to this one.
Video production has also been slowed both for personal reasons (I have a lot on for the remainder of the year), and because PowerDirector 365 has been buggered by recent updates to the point where I may actually have to give up on it and go learn how to use a wholly new editor package.
But then, if dull nonsense such as this is all I have to offer going forward, is it worth it one wonders?
New Toys shown in this presentation:
Runprotec cable spooler:
https://www.tlc-direct.co.uk/Products/RUN10137.html
Keter collapsable workbench:
https://www.toolstation.com/keter-folding-work-bench/p10910
Sebson MR16 12V PAR16 LED lamps [affiliate link]:
https://amzn.to/3G26Y1L
Long Life Lamp Company 12V MR16 spike lights [affiliate link]:
https://amzn.to/3QUn8AH
Slimline no-balls electric screwdriver [affiliate link]:
https://amzn.to/49uYVbs
Wooden dowels, 6x30mm (use 5.5mm masonry drill):
https://www.toolstation.com/wooden-dowel/p75364
Knightsbridge IP68 T-connectors [affiliate link]:
https://amzn.to/3QTdVJ0
Flex stripper (not the Knipex Ergostrip) [affiliate link]:
https://amzn.to/3MFVN2u
The timer used was branded as Green Brook and can be found in the likes of Toolstation:
https://www.toolstation.com/greenbrook-digital-din-rail-mounting-timer/p83052
...or rebranded as MCG at CEF:
https://www.cef.co.uk/catalogue/products/4574801-24-hour-7-day-single-channel-1-module-digital-din-rail-timer
The photocell was also something available at either Toolstation or CEF:
https://www.toolstation.com/miniature-photocell-ip20/p62310
https://www.cef.co.uk/catalogue/products/620857-10a-remote-miniature-photocell
The LED driver was a generic model. I normally buy Sebson units from Amazon [affiliate link]:
https://amzn.to/3FXcZNu
Related videos:
SWA Splicin’ and SELV garden lighting:
https://youtu.be/xNG6SFiMwAI?si=FmyErt91pzgEBhYA
The Garo shower priority unit (mentioned in the coffee shouts):
https://youtu.be/N_jTZbpUfTc?si=cOKpFHpFsy6X9pPD
Affiliate links:
For a shout out in a future video, you can buy me a cigar here or with the SuperThanks button:
https://www.buymeacoffee.com/dseselectric
What’s left of my Amazon storefront:
https://www.amazon.co.uk/shop/davidsaveryelectricalservices
£50 off YourTradeBase:
https://go.yourtradebase.com/refer/3M6F3301
SumUp credit/debit card processing:
http://r.sumup.com/referrals/oBF5S
Get £40 credit for switching to Zen Internet:
https://zen.mention-me.com/m/ol/rt4lh-david-savery
For web hosting, get £10 off at Krystal with the code DSESELECTRIC at checkout!
https://krystal.uk/
Recycle your scrap cable at greencable.com - use referral code GREENCABLET1ZT when setting up an account and Ill get a tenner while you get a recycling bin delivered at no cost!
For more on my video content, refer to my OnlyFans page (not really an OnlyFans page):
https://dses.co.uk/index.php/news/244-onlyfans or at dses.tv FFS, *AGAIN* with the SELV spike lighting!](https://i.ytimg.com/vi/Pn6uemLLF1o/mqdefault.jpg)