Uploaded November 2019 | Updated November 2026, 3 hours ago
Our first look at what is a long-term project revamping a listed manor house in Warwickshire and you're in with us on the ground floor of this one! This week saw us putting two days into familiarisation and inspection/testing to find what's there and what state it's all in. The previous owner had said he'd used a proper sparkie in maintaining the thing, but it's in a woeful condition. Filmed over two days, we had a shed-load of video that I've had to edit down to be somewhere manageable but this is a long watch and only part one of two videos on the inspection and testing element, the second of which will be uploaded as soon as I can pull my finger out of my arse.
Warning: contains strong language and scenes of doofusness.
I've listed chapters so that you can cut to the chase if you can't be arsed to wade through the whole goddamned thing:
Chapter 1 (1:00): A peek at where we are
Chapter 2 (7:09): House tour with Hilary, our client
Chapter 3 (17:47): First look at the electrical installation
Chapter 4 (39:36): Circuit tracing
Chapter 5 (55:00): Inspection and testing (the bit you actually want to see, probably).
Previously, people have questioned why time is being thrown at inspecting and testing on an older installation due for refurbishment rather than just rewiring it, and while much of this will eventually be rejigged and replaced, it's not something that's going to happen quickly in the short term. With my extended family living in the place, I want to know it's safe at this time. The installation has been deemed to be 'unsatisfactory' as far as our report goes, but not everything is captured on camera or discussed in this video.
For the musical bit, I wanted to have Bach's Cello Suite No. 1 in G Major, Prelude, but Sony have been dicks about people on YouTube using the music of a composer who's been dead for the best part of 300 years and I couldn't find a royalty free performance, although I could find a licence for £35. It was the same with Delibes Flower Duet as my second choice. YouTube costs me enough in time; I don't want to piss money on it, and I don't want to stuff in a load of adverts to pay for any whistles and bells even on a video this long. So, my thanks go to YouTuber Kabbalistic Village Music for taking the time to provide musical content for creators. Go take a nosey around that channel: youtube.com/channel/UC-9i8ojCTpPp19PGI67TB-Q
...although a copyright claim was logged for this music on 30/05/20 which means I am no longer responsible for any ad interruptions and any revenue for the whole thing now goes to some dipshit record company. Can't say I'm too fussed; in the past six months the ad revenue only added up to £16. Still, it's annoying to get permission to use a piece from the creator only for a bunch of suits to roll up later high-fiving each other over a job well done in filing a successful claim. Well done lads, I'm slow-clapping you right now.
Apologies if the camerawork makes you dizzy, Nige is a menace on the bloody zoom button and has been suitably chastised.
When I moan about the forms about an hour in, I stated there was nowhere to record Zs at DB. The model forms in BS7671 do have a Zs at DB box on the Schedule of Test Results, but Easycert doesn't. The Easycert layout is based on the NICEIC forms, so they're responsible for that omission. That doesn't detract from my point about the certificates and report as defined in BS7671 being unfit for purpose though: they're crap in my opinion.
This video was not sponsored by Unilite. I don't know if I mentioned, but I bought mine for nine quid (ex-VAT) from Denmans. The radios we use are Binatone Action 1100 PMR446 models as seen in this affiliate link: amzn.to/35Gt31Y
Our first look at what is a long-term project revamping a listed manor house in Warwickshire and you're in with us on the ground floor of this one! This week saw us putting two days into familiarisation and inspection/testing to find what's there and what state it's all in. The previous owner had said he'd used a proper sparkie in maintaining the thing, but it's in a woeful condition. Filmed over two days, we had a shed-load of video that I've had to edit down to be somewhere manageable but this is a long watch and only part one of two videos on the inspection and testing element, the second of which will be uploaded as soon as I can pull my finger out of my arse.
Warning: contains strong language and scenes of doofusness.
I've listed chapters so that you can cut to the chase if you can't be arsed to wade through the whole goddamned thing:
Chapter 1 (1:00): A peek at where we are
Chapter 2 (7:09): House tour with Hilary, our client
Chapter 3 (17:47): First look at the electrical installation
Chapter 4 (39:36): Circuit tracing
Chapter 5 (55:00): Inspection and testing (the bit you actually want to see, probably).
Previously, people have questioned why time is being thrown at inspecting and testing on an older installation due for refurbishment rather than just rewiring it, and while much of this will eventually be rejigged and replaced, it's not something that's going to happen quickly in the short term. With my extended family living in the place, I want to know it's safe at this time. The installation has been deemed to be 'unsatisfactory' as far as our report goes, but not everything is captured on camera or discussed in this video.
For the musical bit, I wanted to have Bach's Cello Suite No. 1 in G Major, Prelude, but Sony have been dicks about people on YouTube using the music of a composer who's been dead for the best part of 300 years and I couldn't find a royalty free performance, although I could find a licence for £35. It was the same with Delibes Flower Duet as my second choice. YouTube costs me enough in time; I don't want to piss money on it, and I don't want to stuff in a load of adverts to pay for any whistles and bells even on a video this long. So, my thanks go to YouTuber Kabbalistic Village Music for taking the time to provide musical content for creators. Go take a nosey around that channel: youtube.com/channel/UC-9i8ojCTpPp19PGI67TB-Q
...although a copyright claim was logged for this music on 30/05/20 which means I am no longer responsible for any ad interruptions and any revenue for the whole thing now goes to some dipshit record company. Can't say I'm too fussed; in the past six months the ad revenue only added up to £16. Still, it's annoying to get permission to use a piece from the creator only for a bunch of suits to roll up later high-fiving each other over a job well done in filing a successful claim. Well done lads, I'm slow-clapping you right now.
Apologies if the camerawork makes you dizzy, Nige is a menace on the bloody zoom button and has been suitably chastised.
When I moan about the forms about an hour in, I stated there was nowhere to record Zs at DB. The model forms in BS7671 do have a Zs at DB box on the Schedule of Test Results, but Easycert doesn't. The Easycert layout is based on the NICEIC forms, so they're responsible for that omission. That doesn't detract from my point about the certificates and report as defined in BS7671 being unfit for purpose though: they're crap in my opinion.
This video was not sponsored by Unilite. I don't know if I mentioned, but I bought mine for nine quid (ex-VAT) from Denmans. The radios we use are Binatone Action 1100 PMR446 models as seen in this affiliate link: amzn.to/35Gt31Y

![Hot tubbery with Phil the f@%*ing Plumber
Warning! Contains a plumber: some viewers may find this distressing.
This was one of our first jobs back in the spring following Nige having been on furlough for two months and involves a hot tub going in at the request of our old mukker Phil, who… perhaps… won’t be quite so friendly toward us once he sees this video…
Anyway, there’s a lot of nonsense in this and some ‘mature’ scenes and chatter… so don’t watch it. Seriously, you don’t even get to see the flimmin’ hot-tub at the end. For anyone foolishly ignoring this sage advice, some chapters are below:
00:00 Mindless van-chat.
10:07 Phil the f***ing Plumber.
11:51 Mindless site-surveying chat.
18:25 Drilling an ‘ole.
20:25 Mindless Huel chat.
21:10 Planning the heist.
36:37 Installation begins.
1:08:18 Escape from Grafton Flyford.
Regarding hot tubs, there are different ways and means. We went for a TT install and I explain the reasons why in this presentation. That doesn’t mean it’s big, hard or clever or that we got it right… or for that matter anyone else got it wrong if they’ve done it differently. It’s simply one of those jobs where you refer to many publications to try and figure out just what you’re supposed to be doing as the guidance and manufacturers aren’t terribly helpful.
We used MCG gear from CEF, and the main reason for that being the 100ma Type-S Type-A fault protection RCD was readily available and keenly priced, plus MCG had a low-cost steel enclosure it could be housed in. They also had double-pole RCBOs, 40A C-Curve Type-AC, so it ticked all the boxes. My thanks to Lee at CEF Warwick who pulled out the stops to grab the RCBO for us from another branch at the last minute after I found I’d purchased the wrong one. Lee, we salute you!
The job as planned was for the rotary isolator to be on the back wall facing the field so it would be out of line-of-sight, but on the day, Phil asked us to place it onto the side wall. That left us short of flexi-conduit as we hadn’t brought enough for the new position. A bit of a shame as it’s less aesthetically pleasing. The patio lights are Class II, so no need to worry about simultaneous touch contact between Class I parts and TT earthing.
The testing of the 100mA RCD at the end seems to have been lost. Sorry. That was tested from the output of the device itself as, obviously, if you connect the tester downstream then the 30mA RCBO will get in the way.
My thanks to the following:
Alymazing Karaoke for musical support:
https://www.youtube.com/channel/UCG024cJIVAgbUHvjYV7IiQw/videos
Luko3artist for accepting my commission for the caricature artwork:
https://www.deviantart.com/luko3artist
https://instagram.com/luko3artist?igshid=1dqcbwt0ldsvd
https://www.youtube.com/channel/UCEr4dtAAn2iM9fqLNfqOWbg
Links:
Craig Gifford installing a hot tub using the Matt:e device:
https://www.youtube.com/watch?v=l5DjBRiwCDc&t=3s
Nick Bundy installing a hot tub on PME:
https://www.youtube.com/watch?v=usXBONOMAuQ&t=3s
Huel:
https://huel.mention-me.com/m/ol/nm0sq-david-savery
Electricians Guide to the Building Regulations:
https://amzn.to/38Et1IX [affiliate link]
IET Guidance Note 8:
https://amzn.to/30uQkCP [affiliate link] Hot tubbery with Phil the f@%*ing Plumber](https://i.ytimg.com/vi/OOCGOHFWpEQ/mqdefault.jpg)





![FFS, *AGAIN* with the SELV spike lighting!
It’s a return to basics with this vlog which would perhaps sit more at home with my content from five years ago seeing as there’s no script, no fun, no sound quality etc. I’m afraid it’s all rather been done before, not least in my “SWA Splicing and SELV garden lighting” video from April 2019. One annoyance is that I hung around specifically to be able to show you these lights at dusk, but was ejected from site two minutes after they activated, so there’s not even a satisfactory ending to this one.
Video production has also been slowed both for personal reasons (I have a lot on for the remainder of the year), and because PowerDirector 365 has been buggered by recent updates to the point where I may actually have to give up on it and go learn how to use a wholly new editor package.
But then, if dull nonsense such as this is all I have to offer going forward, is it worth it one wonders?
New Toys shown in this presentation:
Runprotec cable spooler:
https://www.tlc-direct.co.uk/Products/RUN10137.html
Keter collapsable workbench:
https://www.toolstation.com/keter-folding-work-bench/p10910
Sebson MR16 12V PAR16 LED lamps [affiliate link]:
https://amzn.to/3G26Y1L
Long Life Lamp Company 12V MR16 spike lights [affiliate link]:
https://amzn.to/3QUn8AH
Slimline no-balls electric screwdriver [affiliate link]:
https://amzn.to/49uYVbs
Wooden dowels, 6x30mm (use 5.5mm masonry drill):
https://www.toolstation.com/wooden-dowel/p75364
Knightsbridge IP68 T-connectors [affiliate link]:
https://amzn.to/3QTdVJ0
Flex stripper (not the Knipex Ergostrip) [affiliate link]:
https://amzn.to/3MFVN2u
The timer used was branded as Green Brook and can be found in the likes of Toolstation:
https://www.toolstation.com/greenbrook-digital-din-rail-mounting-timer/p83052
...or rebranded as MCG at CEF:
https://www.cef.co.uk/catalogue/products/4574801-24-hour-7-day-single-channel-1-module-digital-din-rail-timer
The photocell was also something available at either Toolstation or CEF:
https://www.toolstation.com/miniature-photocell-ip20/p62310
https://www.cef.co.uk/catalogue/products/620857-10a-remote-miniature-photocell
The LED driver was a generic model. I normally buy Sebson units from Amazon [affiliate link]:
https://amzn.to/3FXcZNu
Related videos:
SWA Splicin’ and SELV garden lighting:
https://youtu.be/xNG6SFiMwAI?si=FmyErt91pzgEBhYA
The Garo shower priority unit (mentioned in the coffee shouts):
https://youtu.be/N_jTZbpUfTc?si=cOKpFHpFsy6X9pPD
Affiliate links:
For a shout out in a future video, you can buy me a cigar here or with the SuperThanks button:
https://www.buymeacoffee.com/dseselectric
What’s left of my Amazon storefront:
https://www.amazon.co.uk/shop/davidsaveryelectricalservices
£50 off YourTradeBase:
https://go.yourtradebase.com/refer/3M6F3301
SumUp credit/debit card processing:
http://r.sumup.com/referrals/oBF5S
Get £40 credit for switching to Zen Internet:
https://zen.mention-me.com/m/ol/rt4lh-david-savery
For web hosting, get £10 off at Krystal with the code DSESELECTRIC at checkout!
https://krystal.uk/
Recycle your scrap cable at greencable.com - use referral code GREENCABLET1ZT when setting up an account and Ill get a tenner while you get a recycling bin delivered at no cost!
For more on my video content, refer to my OnlyFans page (not really an OnlyFans page):
https://dses.co.uk/index.php/news/244-onlyfans or at dses.tv FFS, *AGAIN* with the SELV spike lighting!](https://i.ytimg.com/vi/Pn6uemLLF1o/mqdefault.jpg)