How much working space is required around a fire alarm control unit?
In this third video of our series on fire alarm control unit mounting and installation, we discuss the working space requirements found in NFPA 70, National Electrical Code (NEC).

Working space must be provided around electrical equipment so the equipment can be safely accessed, operated, inspected, and serviced.

The required working space includes:
• Depth: 3 feet (900 mm)
• Width: At least 30 inches (762 mm) or the width of the equipment, whichever is greater
• Height: At least 6.5 feet (2 m)

This working space must be dedicated to the use and servicing of the control unit. It should not be used for storage or other purposes that could obstruct access to the fire alarm control unit.

Stay tuned for the last video in this series, where we’ll cover early warning detection requirements around control equipment.

Always verify the requirements in the edition of NFPA 70 referenced in your jurisdiction, along with local requirements and direction from the authority having jurisdiction.

Important Notice:
Any opinion expressed in this video is the opinion of the author and does not necessarily represent the official position of NFPA or its Technical Committees. In addition, this piece is neither intended nor should it be relied upon to provide professional consultation or services.
How Much Working Space Is Required Around a Fire Alarm Control Unit?What Is Wildfire Community Preparedness Day?Understanding the Fire Pump Bypass: Purpose and Installation ConsiderationsReorganization of the 2029 NECThe History and Evolution of Burn Treatment2026 NEC Changes: Raceways in Wet LocationsThe Connection Between NFPA 70E and NFPA 70BWet Pipe Fire Sprinkler Systems – How They WorkNFPA 70E Ties to OSHABay State Explores Single Exit StairsTrappedFull Throttle
National Fire Protection Association |

How Much Working Space Is Required Around a Fire Alarm Control Unit?

SHARE TO X SHARE TO REDDIT SHARE TO FACEBOOK WALLPAPER