How high should a fire alarm control unit be mounted?
In this second video of our series on fire alarm control unit mounting and installation, we discuss the mounting height requirements found in NFPA 72, the National Fire Alarm and Signaling Code.
NFPA 72 requires fire alarm control equipment to be mounted so that the following are within the required accessible range:
• Visible indicators
• Displays
• Switches
• Controls
These components must be located between 15 inches and 6 feet above the finished floor, or 375 mm to 1.8 m.
Proper mounting height helps ensure that the fire alarm control unit can be easily viewed and operated by responding personnel and other authorized users.
Stay tuned for the rest of this series on fire alarm control unit mounting requirements. In the next video, we’ll discuss working space requirements around a fire alarm control unit.
Always verify the requirements in the edition of NFPA 72 used in your jurisdiction, along with local requirements and AHJ direction.
Important Notice:
Any opinion expressed in this video is the opinion of the author and does not necessarily represent the official position of NFPA or its Technical Committees. In addition, this piece is neither intended nor should it be relied upon to provide professional consultation or services.
How high should a fire alarm control unit be mounted?
In this second video of our series on fire alarm control unit mounting and installation, we discuss the mounting height requirements found in NFPA 72, the National Fire Alarm and Signaling Code.
NFPA 72 requires fire alarm control equipment to be mounted so that the following are within the required accessible range:
• Visible indicators
• Displays
• Switches
• Controls
These components must be located between 15 inches and 6 feet above the finished floor, or 375 mm to 1.8 m.
Proper mounting height helps ensure that the fire alarm control unit can be easily viewed and operated by responding personnel and other authorized users.
Stay tuned for the rest of this series on fire alarm control unit mounting requirements. In the next video, we’ll discuss working space requirements around a fire alarm control unit.
Always verify the requirements in the edition of NFPA 72 used in your jurisdiction, along with local requirements and AHJ direction.