In this video I test a 50A NT00 fuse to see if they blow at the rated current. The test had something surprising. While the fuse element blew, the indicator wire didn't trip. Thats because when the main fuse element blew, the inverter stopped the loads, and the inverter idle power consumption ran through the indicator wire, but it didn't draw enough current to melt the indicator wire. The indicator wire had a voltage drop of 2.5V, and thats why the inverter was not able to power on because of a low voltage error. 13.3V-2.5V=10.8V which is under the low voltage disconnect of the inverter.
When i increased the voltage of the battery, then the indicator wire did trip because the inverter didn't shut down on low voltage. 26.6V-2.5V=24.1V which is above the minimum 22V input voltage of the inverter.
In all tests, the fuse did trip and was successful in protecting the cable.
I talk about the different sizes of NT fuses like NT1,2,3, and 4. And how some fuses are not compatible with other holders, so you have to choose the right fuse for every holder.
These fuses are ideal as a main battery fuse for lithium battery banks from 12 to 48volts. I compare it to a class-T fuse. But you should not use it if you want your system to be UL certified, because this fuse does not have UL certification.
0:00 intro
0:52 3 Reasons why I like these
2:11 international safety standard
3:22 time-current curve explanation
4:54 50A test
6:43 100A test
10:37 200A test
11:46 Indicator wire explanation
13:16 24V 100A Test
15:42 Different fuse sizes
17:38 Where do you buy these fuses?
18:30 Conclusion
Link to the fuses: cleversolarpower.com/go/NTfuses
🔋My recommended batteries: cleversolarpower.com/my-recommended-parts
Link to the Wire and Fuse Calculator: cleversolarpower.com/wireandfusecalculator
📖 My Best-Selling book on Amazon: cleversolarpower.com/off-grid-solar-power-simplified
🎁 Free Diagrams: cleversolarpower.com
In this video I test a 50A NT00 fuse to see if they blow at the rated current. The test had something surprising. While the fuse element blew, the indicator wire didn't trip. Thats because when the main fuse element blew, the inverter stopped the loads, and the inverter idle power consumption ran through the indicator wire, but it didn't draw enough current to melt the indicator wire. The indicator wire had a voltage drop of 2.5V, and thats why the inverter was not able to power on because of a low voltage error. 13.3V-2.5V=10.8V which is under the low voltage disconnect of the inverter.
When i increased the voltage of the battery, then the indicator wire did trip because the inverter didn't shut down on low voltage. 26.6V-2.5V=24.1V which is above the minimum 22V input voltage of the inverter.
In all tests, the fuse did trip and was successful in protecting the cable.
I talk about the different sizes of NT fuses like NT1,2,3, and 4. And how some fuses are not compatible with other holders, so you have to choose the right fuse for every holder.
These fuses are ideal as a main battery fuse for lithium battery banks from 12 to 48volts. I compare it to a class-T fuse. But you should not use it if you want your system to be UL certified, because this fuse does not have UL certification.
0:00 intro
0:52 3 Reasons why I like these
2:11 international safety standard
3:22 time-current curve explanation
4:54 50A test
6:43 100A test
10:37 200A test
11:46 Indicator wire explanation
13:16 24V 100A Test
15:42 Different fuse sizes
17:38 Where do you buy these fuses?
18:30 Conclusion