Matt was called out to a commercial kitchen where the extraction system wasn’t working and without both the intake and extract fans running, the gas valve won’t open, meaning no gas to the cooker.

Another engineer had already diagnosed a faulty contactor, and when I arrived it was pretty clear they were right. The top of the old contactor had burnt out, and luckily I had a suitable replacement with me.

New contactor fitted… but the system still wouldn’t start. 🤔

Time for some fault finding.

After checking the control circuit, I found the start switch was operating mechanically but wasn’t actually making the electrical connection. Once removed, the problem became obvious part of the contact block had physically broken off inside the switch.

Rather than replacing the whole assembly, I was able to move the connections onto the spare set of contacts and get the circuit operating again. ⚡️

While we’re inside the panel, I also take a closer look at how the control circuit works, including:

🔹 Contactor operation and auxiliary contacts 13 & 14
🔹 Start/stop control circuits
🔹 A1 & A2 contactor coil connections
🔹 Thermal overload protection
🔹 Normally open vs normally closed contacts
🔹 What happens at terminals 95/96 and 97/98 when an overload trips
🔹 How the fault indicator operates

A nice example of why replacing the obvious faulty component doesn’t always fix the whole problem sometimes you have to keep following the circuit until you find the second fault.

00:00 The Commercial Kitchen Fault
00:35 How the Intake, Extract & Gas Interlock Works
01:05 The Burnt-Out Contactor
01:42 Testing the New Contactor
02:10 There’s Another Fault…
02:45 Finding the Broken Start Switch
03:22 Testing the Control Circuit
03:55 How the Start & Stop Circuit Works
04:35 Understanding Terminals 95 & 96
05:20 How the Thermal Overload Works
05:55 What Are Terminals 97 & 98 For?
06:20 The Fault Indicator Explained

⚠️ Electrical work should only be undertaken by competent persons. Always follow
appropriate safe-isolation procedures and manufacturer instructions.

🔔 Subscribe for more free electrical training videos youtube.com/c/GSHElectrical?sub_confirmation=1

Videos are training aids for City and Guilds (C and G) and EAL courses Level 1, 2, 3 plus AM2, AM2S and AM2E.

You can follow me day by day on Facebook, Instagram, Twitter and TikTok lookout for "GSH Electrical".

▶️ FACEBOOK facebook.com/gshelectrical

▶️ INSTAGRAM instagram.com/p/BrIhZmrAYGDTmjMdb9lUNQodMevqsbDDki3qpQ0

▶️ TWITTER mobile.twitter.com/gsh_electrical

▶️ TikTok vm.tiktok.com/ZMRBLFdhe

#GSHElectrical #Electricaltrainingvideos
#Electrical #Electrician #FaultFinding #ElectricalEngineering #ControlPanel #Contactor #MotorControl #ThermalOverload #CommercialKitchen #ElectricalFault #ElectriciansOfYouTube
Panel Wiring is NOT for EveryoneWhen do I Need to Replace my Type 2 SPD?More Conductors are Connected Together than you Might ThinkWhat Height Should Kitchen Socket Be?Is this a Gimmick for electricians?Don’t Make a Mistake on Insulation Resistance Testing Your Lighting CircuitKitchen Sockets - Don’t Get it WrongWasn’t the Straightforward LED Upgrade I ExpectedExplained - Airing Cupboards in BathroomsHow to Connect PVC Singles into a Consumer UnitNow this is a Bit of ME 🍺Socket Has a Monster Problem 😱
GSH Electrical |

Panel Wiring is NOT for Everyone

SHARE TO X SHARE TO REDDIT SHARE TO FACEBOOK WALLPAPER