Heat Pump Heating Checks: Thermostat, Aux Heat, Pressures @HVACS
Heat Pump Heating Checks: Thermostat, Aux Heat, Pressures  @HVACS
Uploaded November 2026 | Updated November 2026, 3 hours ago
When a heat pump is running in heating mode, the readings and checks look different from cooling, and that’s where a lot of techs go wrong. In this video, Bryan Orr goes through the key heat pump checks to make before and during heating season, from the thermostat to the gauges.

Thermostat configuration is the first thing to check and the most common cause of a heat pump that won’t heat. The AC runs fine all summer, then the first cold night shows a setting that was configured wrong. Bryan explains why the thermostat should be part of every maintenance visit.

Next is the reversing valve. On most systems, the reversing valve must be energized or de-energized correctly for the system to switch into heat. Hearing the valve click isn’t enough. A valve can’t actually shift without a pressure differential, so the compressor has to be running. Bryan’s practical approach: use thermostat service mode if you have it, run the system in heat for a couple of minutes, and confirm the valve really shifts.

Aux heat comes next. Auxiliary heat should run as little as possible, or customers will see high heating bills. The time it matters most is defrost, when the system switches into cooling mode and blows cold air through the house. That’s when the nuisance calls come in. Bryan explains why making sure the heat strips come on and go off matters more to him than testing defrost on every visit. He also shows his preferred test: power the W call from the outdoor unit with a simple jumper, which also confirms the white wire has continuity between the indoor and outdoor units.

Finally, heat pump pressures in heating mode. Bryan covers where to connect your gauges (the common suction port between the reversing valve and the compressor) and the number one mistake techs make. Low suction pressure in heat mode doesn’t automatically mean the system is low on charge. The colder it is outside, the lower the suction will be. 40°F outdoors in heating is like 40°F return air in cooling. High head pressure in heat mode is usually an airflow problem, not a refrigerant problem, so confirm the airflow before you blame the charge. measureQuick has a heat pump heating mode that flags these readings for you.

---

NEXT VIDEO

Heat Pump Defrost Cycle & Heat Strip Wiring Safety | HVAC Heating Season Preparation
youtube.com/watch?v=0wAhrieYofY&t=126s

KEEP LEARNING

Start here:
hvacrschool.com/start

Free HVAC/R training, tech tips, quizzes, calculators, courses, and more:
hvacrschool.com

Listen to the HVAC School podcast:
hvacrschool.com/podcast

Get the HVAC School app:
hvacrschool.com/apps-page

HVAC School provides free HVAC/R training—primarily for techs, by techs. The goal is not just to collect facts. It is to understand the system well enough to apply what you know in the field.

Questions or corrections? Leave a comment and include the equipment model, measurements, and source when you can. None of us gets everything right, and good measurements beat confident guesses.

This content is educational. Follow manufacturer instructions, use proper PPE and safe work practices, and comply with the codes and standards that apply to your equipment and jurisdiction.
Heat Pump Heating Checks: Thermostat, Aux Heat, PressuresNEW Fieldpiece Analog Manifold GaugesUncovering the Root Causes of Commercial Refrigeration FailuresCopeland Mobile App: The Fastest Way to Check Compressor Discharge Line IssuesThe Heat Trick for Checking Compressor Oil with Roman BaughDeliver High Performance Heat Pump Retrofits w/ David RichardsonHow to Handle Price Objections: HVAC Sales TrainingTech, Mechanic, or Craftsman? Finding Your Fit in HVACCopeland Transcritical CO2 Semi-Hermetic Compressor Explained | AHR Expo 2026ZoomLock PUSH & MAX: Braze-Free Refrigerant Fittings DemoBasics of Testing Electric Heat Strip KitsSubcooling with R-454B: Measurement and Troubleshooting
HVAC School |

Heat Pump Heating Checks: Thermostat, Aux Heat, Pressures

SHARE TO X SHARE TO REDDIT SHARE TO FACEBOOK WALLPAPER