In this live episode, Bryan sits down with Jim Bergmann of measureQuick and NAVAC trainers Zane and Jesse Stewart for a deep, technician-focused conversation about advanced refrigerant recovery. The group covers diverse system types and environments, including low-ambient recovery.

Recovery machines cannot pump straight liquid, which we need to be mindful of during service. That said, vapor-only recovery works fine for small charges, but push-pull recovery becomes worthwhile once a system holds more than roughly ten pounds of refrigerant. Refrigerant and tank contamination, as well as general safety (including tank fill limitations), are a couple of other field challenges worth considering in our recovery best practices.

Some best practices to take away from this episode include attaching to the vapor side of the tank (and inverting it), pulling Schrader cores, using large hoses instead of manifold gauges, and keeping the recovery tank cool to eliminate restrictions.

This episode contains embedded sponsor messages from Refrigeration Technologies, Carrier, Copeland, Santa Fe Dehumidifiers, and TruTech Tools.

Resources:

Don't Overfill Recovery Tank Cylinders the Easy Way Recovery Tank Safety Recovery Tank Capacity Push-Pull Recovery Recovery Best Practices w/ NAVAC HVAC School calculators Submit a podcast question Learn about the GRIT Foundation Purchase your tickets or learn more about the 8th Annual HVACR Training Symposium at hvacrschool.com/symposium.
Advanced Refrigerant Recovery: Best Practices for Diverse Systems and EnvironmentsSame Charge, Different Numbers - Short #306NAVAC SK2SV1 Smart Refrigerant Flow Control Kit Hands-On TestBuilding a Business That Lasts: Why Culture Beats Strategy in HVACR featuring Tony GonzalezHVAC Summer Service Calls: Rushing, Mental Fog & How to Stay on Your GameHVAC Compressor Training | Capacitor Wiring, Hard Start Kits & Voltage DropD-TEK® Pro Demonstration: 0.1 PPM Industry Leading Refrigerant Leak DetectorAdding Plumbing To Your HVAC Business with Nate AgentisWhy Compressors Fail: Diagnosis, Replacement & PreventionA2L Sensors Are the New Diagnostic You Can’t Ignore #ShortsHow to Prevent HVAC Callbacks | Maintenance Service Checklist Explained - Part 1Less Compressor, More Suction Pressure - Short #304